Entropy generation minimization of combined heat and mass transfer devices
By Prakash Narayan, Johannes Lienhard, Syed M. Zubair. 2010
156 citations recorded by the source corpus.
Abstract This paper details a simple procedure by which the entropy generation in simultaneous heat and mass exchange devices can be minimized. Effectiveness for these devices is defined and a new parameter, ‘modified heat capacity rate ratio’ is introduced. It is found that the entropy generation of a combined heat and mass exchange device is minimized (at constant value of effectiveness) when the modified heat capacity rate ratio is equal to one irrespective of the value of other independent parameters. Several typical examples of the cooling towers have been studied to illustrate this concept. A practical application of the concept is also illustrated using a humidification–dehumidification desalination system.
Subfields: Mechanical Engineering, Statistical and Nonlinear Physics
View Paper: https://www.semanticscholar.org/paper/36ec63120774b488e2d4ee03e9712717e390e4ed
How researchers see this paper
The researchers whose trusted networks rank it highest, strongest advocate first. Every researcher gets a different order.
In Mechanical Engineering
In Statistical and Nonlinear Physics
Citations in the corpus
- Effect of entropy generation on the performance of humidification-dehumidification desalination cycles (2010, methodology): “An exergy balance is also calculated for each component and for the cycle as a whole after all cycle states have been determined.”