Performance of Single Pass Earth-Tube Heat Exchanger: An Experimental Study

By Girija Sharan, R. Jadhav. Journal of Agricultural Engineering, 2003

69 citations recorded by the source corpus.

A single pass earth-tube heat exchanger (ETHE) was installed to study its performance in cooling and heating modes. ETHE consisted of 50 m mild steel pipe of 10 cm nominal diameter and 3 mm wall thickness, buried 2.85 m deep below ground. Ambient air was pumped through it for conditioning. Tests were conducted on three consecutive days in each month. The ETHE conditioned 5.6 m3/min of 40.6°C air to 26.6°C in cooling mode, and 8.3°C air to 23.0°C in heating mode. Average COP was 3.3 in cooling and 3.8 in heating mode.

Subfields: Aerospace Engineering, Mechanical Engineering, Renewable Energy, Sustainability and the Environment

View Paper: https://www.semanticscholar.org/paper/23c16ce14669d7c08e17517642712fecc70b7c76