Admittance-Based Stability Analysis: Bode Plots, Nyquist Diagrams or Eigenvalue Analysis?
By Lingling Fan, Zhixin Miao. IEEE Transactions on Power Systems, 2020
120 citations recorded by the source corpus.
In the literature, Bode plots and Nyquist diagrams are used extensively in stability analysis for admittance-based models. In this letter, we demonstrate that eigenvalues obtained from the total admittance lead to accurate prediction of stability while Bode plots and Nyquist diagrams show limitations. A voltage source converter with weak grid interconnection is used as an illustrative example to demonstrate the pros and cons of the three methods applied to <inline-formula><tex-math notation="LaTeX">$dq$</tex-math></inline-formula>-frame admittance matrices.
Subfields: Control and Systems Engineering, Electrical and Electronic Engineering